Prices  UG-5-AFR-230V-Z Calectro Macedonia

BRAND Calectro
Product UG-5-AFR-230V-Z
Description air duct smoke switch
Internal code IMP1310867
Weight 1
Custom code 85311030
Technical specification 230 VAC DIBt The DIBt-approved Uniguard smoke detector is designed to detect smoke in ventilation ducts and combines a smoke detector with an adapter system, with a pipe and housing specifically for a Optimum airflow has been designed by the smoke detector. The UG-5 can be installed on either side of the channel in Four different positions can be installed: 0°, 90°, 180° and 270°. Patented Power supply: 230 V AC -15%, +10% Smoke detector type: UG-5-AFR-230V optical Max. power consumption: 30 mA Operating temperature: -10°C to +55°C Max. humidity: 99% RH Air speed range: 1 to 20 m/s Approvals: VdS G213014, CE, prEN-54-27, DIBt: Z-78.6-232 Smoke alarm unlocking via remote reset Relay output: Potential-free Smoke alarm relay: Two 250 V, 8A switch contacts Service alarm: One changeover contact 250 V, 5 A System fault alarm: One changeover contact 250 V, 5 A Air speed alarm alarm: One switch contact 250 V, 5 A LED on smoke detector: Green: service alarm (contamination) Red smoke alarm LED on circuit board: Green: normal operation Yellow - system error Yellow - air speed alert Adapter housing: ABS Protection class: IP54

default.send_request_amp_Group2